Fire resistance test in Indonesia
Tested in Indonesia by Sucofindo to SNI 1741-2008: a single-leaf steel fire door sample reached −/120/120, meaning integrity and insulation for 120 minutes. The result applies to doors of the same type and materials as the tested sample.
- Standard
- SNI 1741-2008 · −/120/120
- Report no.
- E38326/FNBPAT
- Laboratory
- Sucofindo, Electrical and Engineering Laboratory (KAN accredited, LP-024-IDN)
- Report date
- 2026-08-26
| Integrity | No fire penetration for 120 minutes | No fire penetration; test stopped at 120 minutes |
|---|---|---|
| Insulation: average temperature, unexposed side | ≤ 168.4 °C | 89.5 °C at 120 minutes |
| Insulation: maximum temperature, unexposed side | ≤ 208.4 °C | 106.4 °C at 120 minutes |
| Furnace temperature at 120 minutes (test condition) | Follow the SNI 1741-2008 standard curve (1,049.0 °C at 120 minutes) | 1,038.8 °C, deviation −1.0 % from the curve |
Applies to: Steel & Fire Door